Monday, 25 July 2016

SF6 properties

Ever Wondered Whats so great about SF 6 ? 

More on Circuit Breakers

Let us learn about Operating Duty of a CB
Various components of circuit breaker take different operating time 

Wednesday, 20 July 2016

More on Circuit Breakers

Some common problems encountered in CBs:

Make                                     Problem

ALIND................................. Chain

CGL interruptor.....................Tripping latch lever

Energoinvest  int....................Blocking lever and Coupling

Merlin German Inturrptor......C & D Rollers.


Now lets see some test reports of 25 KV single pole VCB:




Circuit Breaker Maintenance

Some ratings for knowledge:
Spring charge motor   DC 220 V




Coils  : Shunt Trip  110 V Dc
                Closing Coil   110 V Dc


There are three types of maintenance:
Corrective, Preventive and Predictive.

The governing IS for CBs:

  • Routine test as per IEC 60065/IS 13118
  • Testing alongwith panels to be tested as per IEC 60298/ IS 3427



Shown above is a 12 KV VCB, 1600 A, 25 kA

Interrupter Assembly:

  • contacts
  • arc interrupters
  • arc chutes
Operating assembly
Operating rod
control panel
sealing system

Breaking Medium
  • SF6
  • Oil
  • Vacuum and Air 



Auxiliary Equipment  :   Alarm Scheme, Annunciator etc\

What checks we should carry out in a traction substation regarding CB and interruptor?

Friday, 8 July 2016

Lets learn about Batteries

Batteries have evolved over recent past, some types:
 

Other types as follows:



 Shown above is 650 Ah VRLA battery.



Earthing

I.E. Rules 61  :   substation and equipments

I.E. Rules 67 : HV and EHV

Maxm Res. :
Large power stations   0.5 ohms
Major Substations      1.0 ohms

Small Substations    2.0 ohms
Others                       8 ohms


I.E. Rules  1956 Chapter I 

Low :          250 V
Medium:    650 V
HV:           11 KV
EHV:         33 KV

A note about slip test

It is conducted to calculate unsaturated Xd and Xq.
We feed subnormal voltage to armature, mechanically rotate  it, keep field open ( Vf) 
Here Nr is not equal to Ns.
but is almost equal to Ns.
Since mmf due to armature reaction is rotating at Ns, field poles gradually slip w.r.t. rotating armature mmf.
Thus R = 1/ u of path of mmf changes at twice slip freq. from maxm when axis of poles and axis of armature reaction  wave coincide and minm. when they are at right angles.

MCQs on Electrical Engineering

Q. The phase sequence of alternator wil reverse when 

  • I(f) is reversed, keeping direction of rotation as same.
  • I(f) remains same, direction of rotation is reversed.
  • I(f) reversed, P x2 
  • P x 2 ,  I(f)  same 

More about Transformers

The weakest link in the transformer is  Cellulose !

Condition of Cellulose depends upon Moisture, Temp and Oxygen.

Due top weak Cellulose, Partial Discharge  and creepage failures occur.

There is something called piper chart (H2O in paper Vs H2O in oil)

water in paper increases parabolically with water increase in oil.

                              Oil                            Paper
New T/F                  1                               1000
Old T/F                   1                                  500


 A typical 220 KVA T/F will have 56 T oil and 6 T paper.
 

Lets Learn about Transformers