Wednesday, 8 January 2014

Some notes on HVDC

Advantage of ground retuyrn:


  • Earth resistance in case of dc for long lines is interdependent of length and this resistance is < that of metallic conductor if used.
  • d.c line can be built in two stages.
  • reliability increases in case of outage one monopolar out of the bipolar.


Disadvantages of  ground return:

  • Electrolytic erosion of buried / immersed metallic structure.
  • difficult design
  • Ground currents can cause dangerous step and touch voltages.
  • Ground current interferes with other services.

Saturday, 22 December 2012

Ohm's Law and kirchoff's law


Ohms law:
v(t) = i(t) R  - or -  V = I R
p(t) = i2(t) R = v2(t)/[+ (absorbing)]
Kirchoffs law:

Kirchhoffs Current Law (KCL)

sum of all currents entering a node is zero

sum of currents entering node is equal to sum of currents leaving node


Kirchhoffs Voltage Law (KVL)
sum of voltages around any loop in a circuit is zero
Kirchoffs Current Law :

The sum of currents entering the node is zero:

Analogy: mass flow at pipe junction


KVL Polarity
A loop is any closed path through a circuit in which no node is encountered more than once
Voltage Polarity Convention
A voltage encountered + to - is positive
A voltage encountered - to + is negative


Electrical Analogies (Physical)






Thursday, 20 December 2012

Basic Electrical Quantities


Basic quantities: current, voltage and power
Current: time rate of change of electric charge
  I = dq/dt 
1 Amp = 1 Coulomb/sec
Voltage:  electromotive force or potential, V 
1 Volt = 1 Joule/Coulomb = 1 N·m/coulomb
PowerP = I V 
1 Watt = 1 Volt·Amp = 1 Joule/sec

Active elements can generate energy
–Batteries
–Voltage and current sources
Passive elements cannot generate energy
–Resistors
–Capacitors and Inductors (but CAN store energy)
An independent source (voltage or current) may be DC (constant) or time-varying, but does not depend on other voltages or currents in the circuit.
The dependent source magnitude is a function of another voltage or current in the circuit.





Monday, 26 November 2012

A motor problem

Q) A 25 HP 6 Pole 50 Hz 3 phase 960 rpm at full load. I 2 = 35 A, Allowing 250 W as Cu loss in SC gear . 1000 W = Mech losses.
How much is r2?
Ans)

Q) 440 V , 50 Hz, 6P, 3 phase, 

Ans) F2 = 100/60 




Monday, 5 November 2012

RL circuit on a AC source.

In the previous post we had seen RL circuit on DC source. Now lets see it on AC source




Transients in power system

Transients in simple circuit

DC Sources:




  • Resistance only
  • Inductance only
  • Capacitance only

  • RC Circuit

  • RLC Circuit:



Sunday, 4 November 2012

How to control voltage in power system









































We have seen total grid collapsing twice recently. How voltage is controlled? Lets see in the above diagram


Sources and sink of Reactive power



  • Transmission line
  • Cables
  • Synch. Machines
  • Shunt capacitors and reactors
  • Series capacitors

Wednesday, 31 October 2012

Insulated Cables




Capacitance of three core cables



Grounding

Advantages of neutral grounding:

  • Voltage of phases are limited to phase to ground voltage.
  • High voltages due to arcing grounds or transient line-ground faults are eliminated.
  • Sensitive protective relays against LG faults can be used.
  • Overvoltages due to lightening are discharged to ground.
Advantages of isolated neutral

  • It is possible to maintain supply with fault on line.
  • Interference with communication lines is reduced because of no Z sequence current.
Effective grounding systems:

X0 / X1 < 3

Least Expensive is = maxm Vphase= 0.8 V line







Tuesday, 30 October 2012

Series or Shunt Capacitor

Voltage Boost:

Shunt Capacitor: Evenly distributed over transmission line.

Series Capacitor: -----------------------I  I-------------------------
                                                   V1            V2
                                     Sudden change of voltage



  • Shunt Capacitor improves power factor of the load whereas Series capacitor has little effect on pf.
  • For long transmission line, where total reactance is high, series capacitors are effective for improvement of system stability.


Monday, 10 September 2012

How to measure Flow?

Flow Strainers, Impellers, Magnetic sensing pickups. 

Turbine Meter

  • good for telemetry
  • errors may be caused 'coz of excessive frictional torque.
Electromagnetic flowmeter
  • suitable for slurry, sludges etc
  • Adv: size adaptability,No pressure drop
  • Disad: for heavy slurry, high operating cost.
Hot Wire Anemometers

  • more flow > more cooling
  • voltage variation
  • measured by POT

Using Thermister

  • can measure velocity of air

Ultrasonic flow meter

  • used mainly for liquid
  • useful for bidec tional flow
  • Adv:linear relationship
  • Adv:insensitive to variation in viscocity, density and temp
  • Disadv: complexity
  • Disadv: relative high cost






Per Unit Impedance


Saturday, 8 September 2012

Some EE Questions

Q) For eleiminating 5th harmonics in a three phase AC system, the winding pitch should be?

Choices:   2/3, 4/5, 5/6, 6/5

Q) Magnetic circuit is saturated, delivering full load current at rated volt and current. n= constant, brushes at interpolar axis. When load is switched off, terminal voltage would?

Choices:  remain same , increase, decrease, will become 0.

Q) Under which of the following conditions dc motor with compensating winding is used?

Choices:
A) Wide range of speed control above normal
B) Wide range of steady load variation with no speed control
C) Wide range of rapid variation in load

Q) What happens when field of DC shunt motor gets opened?

Q) Match?

Interpoles.................Commutation in D C machine.

Three pt. starter.........DC shunt motor

Dummy Coils............Wave Winding

Equaliser Ring...........Lap Winding

Q) The phase sequence of alternator will reverse when

a) If ( field current) is reversed, keeping direction of rotation same.
b) If remains same, direction of rotation is reversed.
c)If reversed, number of poles is doubled.
d) Number of poles doubled, If same.


Monday, 11 June 2012

Some news in Electrical Engineering


  • Now Low Fire Hazard Cables are available in India. Uniflex has come up with this product.
  • Drawing outsourcing has begun in India as BHEL-Jhansi has done it for 220 kv Power Transformers.
  • Rs 400 Crore capacitor industry in India is growing @ 8 % p.a. 
  • Use of PTC thermistor in the refrigerators saves lots of energy.
  • Now India is equipped for 1200 KV transmission lines.
  • After heat shrink, cold shrink technology is also here.
  • What are PMUs? Ans) Phasor Measurement Units installed in the power grid. 


Friday, 27 April 2012

Electric Heating and Welding

Q) What is difference between types of electrical heating?
Ans) Resistance Heating is done at power freq. while Induction Heating and Dielectric Heating is done at high freq.

Q) Why adjustable AC voltage is used for Salt Bath Furnace?
Ans)Slat Bath Furnace ( No oxidation while hardening)  is used for Steel Tools Hardening at 20 V, 3000 V AC ( DCcan cause electrolysis of NaCl solution). Since Resistance drops with temperature, Adjustable voltage is needed.

Q) Why Heating Materal/Element should have high sp. resistance?
Ans) So that short length of wire is enough.

Q)Why heating element should be free from oxidation?
Ans) Otherwise life will be short. ( Iron addition means oxidation)

Q) Why heating element should have low temperature coeff of resistance?
Ans) So that R does not change much with T.

Q) What are common heating materials?
Ans) Ni-Chr, Ni-Chr-Fe, Ni-Chr-Al, Ni-Cu.




More on Magnetic materials

There are Three types of SOFT MAGNETIC MATERIALS:-
  • Solid Core Material :- These are parts of magnetic circuit carrying steady flux as core etc. Made of Soft iron, relay steel;.
  • Electrical sheet and strip
  • Special Purpose Alloys
Solid Core Materials

  • Iron, Low Carbon, Si Steel  ( Carbon is harmful it raises ciercive force & hystersis loss. Silicon is also harmful but with oxygen it becomes good)
  • Low Carbon Steel ( Steel has low resistivity and high edddy current losses)
  • Cast Iron :- Low relative permeability.
  • Gray Carbon:- Magnetically inferior to wrought iron or steel.
  • Cast Steel:- Used for those portions of magnetised circuits which carry steady flux and need superior mechanical quantities.
  • Soft Steel:-now widely used in place of cast steel.
  • Ferro Cobalt:-It has its saturation flux density 10 % higher than that of pure iron. Cost is High. Use is limited to pole pieces where a huge value of induction ( flux density) is desired.

Sheet Steel:-
Electrical Sheet Steel ( Non-Oriented):- Iron with low Carbon was used earlier. It was prone to ageing. Use of Silicon Steel, this is no issue. Advantages of adding Silicon ( More age, less hysterisis loss, increased resistivity, less eddy current loss). Disadvantages ( loss of permeability at higher flux densities & lower ductility). Hence Maxm Si = 5%
Electrical sheet steel can be Hot Rolled or Cold Rollled. In rotating parts we use steels of low Si content and are called "Dynamo Grade Steel" ( since these have to work at high flux densities).
4 to 5 % Si steel = "Transformer grade Steel"( also called high resistance steel (HRS))


CRGOS:- Saturates at a later stage . Constituent crystals, crystalline axis, cold reductions, annealing. Rolling direction = direction of high permeability.Reduces Iron loss.

Special Purpose Alloys:- SPA , HULOB.
They have high flux permeability at very low flux densities. Ni ( 60 to 90%) + Chr + Mb.
MUMMETAL :- Low permeability but high eddy currrent losses. Some Cu too.
PERMALLOY:High Ni (80%) permalloy ( high initial & maxm permeability , Mb + Cr , High resistivity) Low Ni (50%) Permalloy ( low permeability, high resistivity)
SUPERPERMALLOY:- High Purity, Relative permeability 100,000
PERMINVAR:- Permability independent of field strength.
PERMEANDER:-Capable of producing high flux density 49 % Cobalt 2 %, Vn 49 %

Friday, 20 April 2012

Factors to Be considered in Design

Transformer Design
  • Calculation of leakage reactance.
  • Core dimension.
  • Window Dimension.
  • Frame Size
  • Conductor turns, size.
  • Cruciform dia etc.
  • Hw/Ww, Kw, Stacking Factor
Motor Design
  • Main dimensions. ( alternator)
  • Speed Limitations (alternator)
  • Air gap length, Tph etc.(alternator)
  • SCR L/T (alternator).
  • Bar etc of Induction Motor.

A Note On Magnetic Materials